SEISMIC ALARMS By Dascor

Features

  • Detection levels of 2, 5, or 10 G’s
  • One, two, or three orthogonal axis
  • Individual alarm levels for each axis
  • Two relay control lines per axis, one with a reset timer
  • Control lines normally active high
  • Control lines supply up to 20 mA
  • Status LED’s on all control lines
  • Any failure causes circuit to fail-safe (open relay)
  • Auto-zero circuit
  • Timer reset setable from 1 to 60 seconds
  • Master alarm trips on any axis or out-of-range temperature
  • I/O lines fused and TVS protected
  • Requires 12-24 VDC power at 25 mA plus poser to activate relays
  • Alarm levels set at factory, no field changeable settings
  • Status LED’s for internal power and "heartbeat"
  • NEMA-4 polycarbonate enclosure

OPERATION

Responds to motion in one, two or three axes that are typically caused by seismic events - i.e. earthquakes. When coupled to optically isolated power relays, the device will act to shut down equipment when pre-selected acceleration levels are exceeded.

Each axis senses acceleration by means of a machined silicon accelerometer. The signal is conditioned and amplified to give a high level analog signal for each axis. The signal is then filtered and passed to an Analog to Digital converter in the microprocessor where it is continually measured and compared to programmed alarm limits.

Changes in zero due to temperature drift and slow changes in level or positioning are eliminated by an auto-zero circuit. This feature can be bypassed by means of a jumper. Changes in gain are corrected in the microprocessor based on temperature coefficients provided by the sensor manufacturer and an on-board temperature sensor.

When an alarm limit is exceeded, the appropriate circuits are de-engerized and the associated optically isolated relays open. A master alarm circuit is provided that opens when the processor detects an error condition or time-out. The relay is actuated by any combination of temperature, or motion which exceeds the preset limits. The relays for each axis are triggered only by motion of the axis exceeding the specified limits.

The outputs of the sensor/processor card are active high and are turned on after the preset elapsed alarm time has expired following power-up, or a seismic event. The 5-volt outputs drive a set of industry standard optically isolated power relays. All of the outputs can be considered as "normally closed" position when no alarm conditions exist. Any alarm condition will open the relay contacts. Breaking the external circuit.

Specifications

Acceleration Levels

2, 5 or 10 G’s

Sensitivity

Response Time

Accuracy

Resolution

Input levels

Output levels

Operating Temperature

-40 to +85 Deg. C

Temperature Compensation

0 to 50 Deg. C

Alarm reset interval

1 to 60 seconds

Auto zero

box size

6.75 x 4.75 x 2.25 in